Depot CP 2 Pole Exam Road Depot Contactor Panel - 500A or 630A 630V DC
L.C. SWITCHGEAR LTD.
+44 (0)1273 770540

Depot CP 2 Pole Exam Road Depot Contactor Panel - 500A or 630A 630V DC

Product Image

Depot CP – 2 Pole Exam Road Depot Contactor Panel - 500A or 630A 630V DC

 

Application – on load

The 630V DC is then fed directly from the Contactor to the Road Shore Supply for the Overhead Switchable Trolleys (8800290) OR to the Lifting Shed Power Pedestals (8800291).Used on London Underground

 

The 630V DC is fed to the 2 pole contactor via:

4 pole Isolating & Bonding Disconnector, which has interlocks for Maintenance and Secure Isolations. These prevent contactor operation and the 630V DC supply when maintenance is being performed.

The Contactor provides signals to the Overhead Status Indicators OSI and the Mimic Panel in the DDM Office.

When the Disconnector is moved to the Earthed position the outgoing supplies to the Examination or Lifting Sheds are earthed and can be locked, making them safe for maintenance.

Contactor

Traction grade bar type 500A or 630A 2 Pole Contactor

Fuse

Positive and negative traction grade fuses

Switch

One (1-0-E) 4 pole Manual Off Load, switch

Pad lockable handle

Interlock facility for the bonded position & open positions.

Features

IP54

Protected for internal use

60mm Electrical Clearance

Anti-Condensation paint

Installation

Plinth mounted, 630V DC supply is derived from the bus bar chamber at the bottom.

Cabling

2 x 250mm2 Incoming Traction Positive cables

2 x 250mm2 Outgoing Traction Positive cables

 

Shed Board Isolator

Application – Off Load

The 630V DC is fed from a Shed Board Isolator (8800287) via bus bars which connect into the suite of Contactor Panels. This is interlocked with the contactors so that all of the contactors will de-energise if the isolator is operated ensuring off load operation.

Cabling

1 x 935mm2 Incoming Traction Positive cable

1 x 935mm2 Incoming Traction Negative cable

 

 

 

 

 