Depot CRCP 2 Pole Depot Cleaning Road Contactor Panel - 500A or 630A 750V DC
L.C. SWITCHGEAR LTD.
+44 (0)1273 770540

Depot CRCP 2 Pole Depot Cleaning Road Contactor Panel - 500A or 630A 750V DC

Product Image

Depot CRCP – 2 Pole Depot Cleaning Road Contactor Panel - 500A or 630A 750V DC

Application – on load

These 630V DC bus bars are connected into a suite of Contactor Panels and the incoming supply to these bus bars is fed by a Shed Board Isolator (8800287). The 630V DC is then fed directly from the Contactor to the Cleaning Road conductor rails. The 630V DC is fed to the 2 pole contactor via: 4 pole Isolating & Bonding Disconnector, which has interlocks for Maintenance and Secure Isolations. These prevent contactor operation and the 630V DC supply when maintenance is being performed.

The Contactor provides signals to the Cleaning Road Overhead Status Indicators COSI and the Mimic Panel in the DDM Office.

When the Disconnector is moved to the earthed position the outgoing supplies to the Cleaning Road Conductor Rails earthed and can be locked, making them safe for maintenance.

Control of the contactor supply can be done at a remote control panel at the end of the road or at local control buttons at the contactor in the Switch room.

The contactor panel is interlocked with the Depot Fire Alarm, Sump Pumps and Flood Sensors Used by London Underground

 

Contactor

Traction grade bar type 500A or 630A 2 Pole Contactor

 

Fuse

Positive and negative traction grade fuses.

 

Switch

One (1-0-E) 4 pole Manual Off Load, switch.

Pad lockable handle

Interlock facility for the bonded position & open positions.

 

Features

IP54

Protected for internal use

60mm Electrical Clearance

Anti Condensation paint

 

Installation

Plinth mounted, 630V DC supply is derived from the bus bar chamber at the bottom.

 

Cabling

1 x 935mm2 Outgoing Traction Positive cable

1 x 935mm2 Outgoing Traction Negative cable

Remote Control Panel

Shed Board Isolator

Application – Off Load

The 630V DC is fed from a Shed Board Isolator (8800287) via bus bars which connect into the suite of Cleaning Road Contactor Panels. This is interlocked with the contactors so that all of the contactors will de-energise if the isolator is operated ensuring off load operation.

Cabling

1 x 935mm2 Incoming Traction Positive cable

1 x 935mm2 Incoming Traction Negative cable

Cleaning Road Overhead Status Indicator COSI 8800292

The overhead status indication of the conductor rail 630V DC power

 

 

 